category filters
Oil & Gas Products

Water Management

Industrial Controls

  • We are here to help.

    Our dedicated staff in Boerne, Texas is available to answer questions about Electrolab products and services.

  • For more info, call:

    1 888 301-2400

    Monday-Friday: 7am-4:30pm Central Time

  • Email Us
  • Find a Distributor
  • Support

Model 3005 Single Channel Analog Board

Model 3005 Single Channel Analog Board

Categories: Legacy Products

The Model 3005 Analog Converter Board is designed to provide a single analog output for our Digital Level Sensors (DLS).


Request for Quote

(Please include all of the specifications from the Configuration Options below on your RFQ)

The Model 3005 Analog Converter Board is designed to provide a single analog output for our Digital Level Sensors (DLS). This board interfaces with the DLS and provides a 4-20mA signal output for the total fluid level of the tank (instead of the standard RS-485 communications). As an alternative to the Model 1000 terminal unit, it is intended for use when an analog signal for the tank level is required and where only one or two tanks are on location.

The Analog Converted Board replaces the fuse board in the explosion-proof housing on top of the DLS and provides the same electrical protection. The board requires 24 VDC and controls power to the level sensor. It powers the sensor on a programmed schedule, polls for the tank level value, powers the sensor down and outputs the analog signal. The configuration information for the Analog Board are stored in the digital level sensor's EEPROM, allowing for easy board replacement, if required.

3005 Wiring Diagram

Operating Specifications

Operating Temperature: -40°F to 185°F (-40°C to 85°C)

Power Supply: 24 VDC ±10%

Maximum Current Drawn: 125 mA

Wiring: Requires two wires for power and two wires for 4-20mA loop 4-20mA conversion accuracy (except as limited by sensor and protocol resolution)

Resolution and Monotonicity:16-Bit

Maximum Integral Nonlinearity:±0.012% max

Maximum Offset:±0.05% max

Maximum Total Output Error:±0.15% max