Model 1060 Low Pressure Pump Cut-Off

Model 1060 Low Pressure Pump Cut-Off

Categories: Legacy Products

The Model 1060 is our low pressure pump cut off. It responds to a switch closure indicating low pressure by cutting off the inlet flow of water from a pump.

Note: This product is no longer available through Electrolab. Information is provided here for technical reference only. For additional information, contact Watts Water Technologies by clicking on this link or call 1-800-659-8400.


Request for Quote

(Please include all of the specifications from the Configuration Options below on your RFQ)

The Model 1060 responds to a switch closure indicating low pressure by waiting an uninterrupted 5 seconds during an alarm condition and then cutting off the inlet water solenoid and pump together and turning on a red light indicator warning of an alarm condition. The time to stay off is adjustable from 10-80 minutes and may be set in 10 minute increments to allow the pump to recover.

The tank level and interlock turn off the loads and turn on the yellow lamp with open circuits, which are factory-set jumpers. These alarms override the low pressure alarm.

Specifications

Housing dimensions: 30 cm x 20 cm x 13 cm

Power requirements: 120/240 VAC in, selectable

Current maximum: 30 Amps AC or 120 VAC (with standard Picker PC739 relay pump)

Horsepower: 1.5 hp or 3 hp at 240 VAC